Journal of Wind Engineering and Industrial Aerodynamics | 2021

Analysis of wind-induced responses and GLF for super-large cooling towers

 
 
 
 

Abstract


Abstract Based on wind tunnel tests, time-varying wind pressure distribution on the finite element model of a super-large hyperbolic cooling tower under group-tower environment were reconstructed by the radial basis function (RBF) method. The results were applied in time-domain calculations of wind-induced responses of the cooling tower. Then, the gust loading factor (GLF) method adopted in current engineering practice was analyzed. The results indicate that: due to some inevitable limitations, the existing GLF scheme, in which a unified amplification factor G is adopted to calculate the equivalent static wind loads, may not be applicable for super-large cooling towers.

Volume 208
Pages 104430
DOI 10.1016/j.jweia.2020.104430
Language English
Journal Journal of Wind Engineering and Industrial Aerodynamics

Full Text