Archive | 2019

Estimation of sensible and latent heat based on measurements for non-typical large room

 
 

Abstract


The knowledge about dynamic changing heating and cooling load in existing building is essential for proper energy management. Whenever existing building is analyzed or ventilation system is going optimized, it’s essential to estimate temporary sensible and latent heat based on historical data. The basic conditions for heat calculations are quasi-stable thermal conditions. If supply air temperature significantly varies in short time, what happens very often, the calculations can give untrue results. The procedure described in this article improves usability of measured data affected by rapid supply air temperature changing. Therefore real sensible and latent heat can be calculated, what it is important for future optimization process. Specified, on the basis of varying supply and exhaust air temperatures, thermal loads range from -55.8 kW to 40.7 kW was substitute to more authentic range from -14.1 kW to 51.2 kW received from the conducted simulations. In addition, the data obtained from the simulation showed that latent heat gains were associated with the air temperature in the room, and not with the operation mode of the ventilation unit (day/night) as observed on the basis of historical data.

Volume 116
Pages 85
DOI 10.1051/e3sconf/201911600085
Language English
Journal None

Full Text