Experimental heat transfer coefficient during condensation of R-410A in horizontal micro-fin tubes

 
 

Abstract


Condensation heat transfer coefficient has been calculated experimentally in microfin tubes of outer diameter 9.52mm with helix angles 15° and 18°. Condensation of refrigerant R-410A include mass fluxes from 200 to 600 kg/m2s, vapour qualities between 0.1 to 0.9 and saturation temperature at 35 °C and 40°C. The experimental results indicate that the average heat transfer coefficients of R-410A in micro-fin (MF) tubes were increased 1.15-1.47 times larger than those of smooth tube (ST). The experimental results are compared with the existing correlations of heat transfer coefficient proposed by other authors. The comparison indicated good agreement with these existing correlations within ±30%. A correlation has also been developed for predicting condensation heat transfer coefficient in micro-fin tubes.

Volume 1240
Pages 12052
DOI 10.1088/1742-6596/1240/1/012052