Journal of Physics: Conference Series | 2021

Research on PD monitoring and location method of automatic directional substation

 
 
 
 
 
 

Abstract


The accurate positioning of partial discharge can effectively avoid the occurrence of insulation failure of power equipment, but most of the existing positioning devices are fixed antenna array, which is difficult to achieve multi angle discharge monitoring in space, and the positioning method is single and the positioning accuracy is not high. Therefore, this paper proposes an automatic directional monitoring device for partial discharge source, and proposes a precise positioning method based on fixed point iteration method. With this positioning method as the main method and the automatic directional device as the auxiliary method, the spatial multi angle positioning of partial discharge source is realized. Firstly, PD signal recognition algorithm is used to identify the fault of PD signal, and then the steering gear rotation angle is determined by the angle correlation calculation formula, so as to accurately identify the position and direction of PD source. On this basis, four antenna array positioning algorithm is used to accurately locate PD source. Finally, through the field simulation test, it is found that the angle error of automatic orientation is 3°. The position error of PD source is 0.19m, which verifies the feasibility of the proposed method and device.

Volume 2005
Pages None
DOI 10.1088/1742-6596/2005/1/012241
Language English
Journal Journal of Physics: Conference Series

Full Text