2019 IEEE 15th Brazilian Power Electronics Conference and 5th IEEE Southern Power Electronics Conference (COBEP/SPEC) | 2019

Inherent Redundancy of SDBC-MMCC based STATCOM in the Overmodulation Region

 
 
 
 
 

Abstract


The single delta bridge cell modular multilevel cascaded converter (SDBC-MMCC) has emerged as an interesting topology for Static Synchronous Compensator (STATCOM) applications. Since this converter is composed of tens/hundreds of components, reliability issues arise and redundant cells must be employed to fulfill the reliability requirements, increasing the initial cost of the STATCOM. In fact, there is a potential for fault tolerant operation when the overmodulation region is considered. This work aims to explore the inherent redundancy of SDBC-MMCC in the overmodulation region. Initially, the boundary conditions between linear and overmodulation region are analytically derived. Then, the inherent fault tolerance is evaluated based on 17 MVA/13.8 kV SDBC-MMCC based STATCOM case study with 24 cells per cluster. The results indicate that the converter is able to exchange rated power with the grid after 1 failure, with harmonic distortion within the limits suggested by the standards.

Volume None
Pages 1-6
DOI 10.1109/COBEP/SPEC44138.2019.9065447
Language English
Journal 2019 IEEE 15th Brazilian Power Electronics Conference and 5th IEEE Southern Power Electronics Conference (COBEP/SPEC)

Full Text