2019 Advances in Science and Engineering Technology International Conferences (ASET) | 2019

Thermodynamic analysis of geothermal series flow double-efffect water/LiBr absorption chiller

 
 
 
 
 

Abstract


In this work, a thermodynamic analysis of a double effect water/LiBr absorption chiller of series configuration powered geothermal energy is presented. The geothermal energy is used to drive the desorber of the absorption chiller. This geothermal energy is obtained from the geofluid leaving an existing geothermal power plant before it is reinjected back to the ground. The effects of geofluid temperature, geofluid mass flow rate, chilled water temperature, condenser inlet temperature as well as the heat exchangers sizes are investigated to find out the performance of the chiller from coefficient of performance and cooling load points of view. This is done by using the mass flow rate and energy balances of each component of the absorption chiller combined with an Engineering Equation Solver software. The results show that the coefficient of performance and cooling load can reach about 1.32 and 475 kW, respectively under some operating conditions.

Volume None
Pages 1-6
DOI 10.1109/ICASET.2019.8714468
Language English
Journal 2019 Advances in Science and Engineering Technology International Conferences (ASET)