2019 5th International Conference on Electric Power Equipment - Switching Technology (ICEPE-ST) | 2019

Impulse Breakdown Characteristics of Double Vacuum Gaps in Series with Asymmetric Distribution

 
 
 
 
 
 

Abstract


The objective of this paper is to determine the effect of asymmetric distribution on the impulse breakdown characteristics of double vacuum gaps in series. Vacuum interrupters with sphere-plane electrodes were selected in our experiments. The material of the electrodes was Cu. The diameter of sphere electrode was 18 mm and the diameter of plane electrode was 50 mm. The gap distance of the sphere-plane electrodes could be adjusted. A negative standard lightning impulse voltage was applied with the up-down method, by which 50% breakdown voltage U50 was obtained.The experiment results showed that the 50% breakdown voltage U50 of double vacuum gaps is slightly lower than that of single vacuum gap when the total gap distance is less than 2 mm. The asymmetric distribution of two gaps has influence on the 50% breakdown voltage U50 of double vacuum gaps, the U50 of double vacuum gaps increases with the upper gap distance under a certain total gap distance. Compared with the lower gap distance, the upper gap distance has a greater effect on the 50% breakdown voltage U50 of double vacuum gaps.

Volume None
Pages 421-424
DOI 10.1109/ICEPE-ST.2019.8928668
Language English
Journal 2019 5th International Conference on Electric Power Equipment - Switching Technology (ICEPE-ST)

Full Text