Featured researches published by Bruce R. Kinzey.
Archive | 2013
Bruce R. Kinzey; Michael Myer
This report documents a solid-state lighting (SSL) technology demonstration at the parking structure of the U.S. Department of Labor (DOL) Headquarters in Washington, DC, in which light-emitting diode (LED) luminaires were substituted for the incumbent high-pressure sodium (HPS) luminaires and evaluated for relative light quantity and performance. The demonstration results show energy savings of 52% from the initial conversion of HPS to the LED product. These savings were increased to 88% by using occupancy sensor controls that were ultimately set to reduce power to 10% of high state operation after a time delay of 2.5 minutes. Because of the relatively high cost of the LED luminaires at their time of purchase for this project (2010), the simple payback periods were 6.5 years and 4.9 years for retrofit and new construction scenarios, respectively. Staff at DOL Headquarters reported high satisfaction with the operation of the LED product.
Archive | 2012
Bruce R. Kinzey; Michael Myer; Michael P. Royer; Greg P. Sullivan
Occupancy sensor systems are gaining traction as an effective technological approach to reducing energy use in exterior commercial lighting applications. Done correctly, occupancy sensors can substantially enhance the savings from an already efficient lighting system. However, this technology is confronted by several potential challenges and pitfalls that can leave a significant amount of the prospective savings on the table. This report describes anecdotal experiences from field installations of occupancy sensor controlled light-emitting diode (LED) lighting at two parking structures and two parking lots. The relative levels of success at these installations reflect a marked range of potential outcomes: from an additional 76% in energy savings to virtually no additional savings. Several issues that influenced savings were encountered in these early stage installations and are detailed in the report. Ultimately, care must be taken in the design, selection, and commissioning of a sensor-controlled lighting installation, else the only guaranteed result may be its cost.
Archive | 2012
Michael Myer; Russell T. Goettel; Bruce R. Kinzey
A review of five post-top light-emitting diode (LED) pedestrian luminaires installed in New York Citys Central Park for possible replacement to the existing metal halide post-top luminaire. This report reviews the energy savings potential and lighting delivered by the LED post-top luminaires.
Archive | 2011
Michael Myer; Bruce R. Kinzey; Ku'uipo Curry
This report describes the process and results of a demonstration of solid-state lighting (SSL) technology in a commercial parking lot lighting application, under the U.S. Department of Energy (DOE) Solid-State Lighting Technology GATEWAY Demonstration Program. The parking lot is for customers and employees of a Walmart Supercenter in Leavenworth, Kansas and this installation represents the first use of the LED Parking Lot Performance Specification developed by the DOE’s Commercial Building Energy Alliance. The application is a parking lot covering more than a half million square feet, lighted primarily by light-emitting diodes (LEDs). Metal halide wall packs were installed along the building facade. This site is new construction, so the installed baseline(s) were hypothetical designs. It was acknowledged early on that deviating from Walmart’s typical design would reduce the illuminance on the site. Walmart primarily uses 1000W pulse-start metal halide (PMH) lamps. In order to provide a comparison between both typical design and a design using conventional luminaires providing a lower illuminance, a 400W PMH design was also considered. As mentioned already, the illuminance would be reduced by shifting from the PMH system to the LED system. The Illuminating Engineering Society of North America (IES) provides recommended minimum illuminance values for parking lots. All designs exceeded the recommended illuminance values in IES RP-20, some by a wider margin than others. Energy savings from installing the LED system compared to the different PMH systems varied. Compared to the 1000W PMH system, the LED system would save 63 percent of the energy. However, this corresponds to a 68 percent reduction in illuminance as well. In comparison to the 400W PMH system, the LED system would save 44 percent of the energy and provide similar minimum illuminance values at the time of relamping. The LED system cost more than either of the PMH systems when comparing initial costs. However, when the life-cycle costs from energy and maintenance were factored into the scenario, the LED system had lower costs at the end of a 10-year analysis period. The LED system had a 6.1 year payback compared to the 1000W PMH system and a 7.5 year payback versus the 400W PMH system. The costs reflect high initial cost for the LED luminaire, plus more luminaires and (subsequently) more poles for the LED system. The other major issue affecting cost effectiveness was that Leavenworth, Kansas has very low electricity costs. The melded rate for this site was
Archive | 2011
Michael Myer; Oindrila Hazra; Bruce R. Kinzey
0.056 per kWh for electricity. However, if the national electricity rate of
Archive | 2010
Michael Myer; Bruce R. Kinzey
0.1022/kWh was used the payback would change to between four and five years for the LED system. This demonstration met the GATEWAY requirements of saving energy, matching or improving illumination, and being cost effective. The project also demonstrated that the Commercial Building Energy Alliance (CBEA) specification works in practice. Walmart appreciated having an entire site lighted by LEDs to gain more experience with the technology. Walmart is reviewing the results of the demonstration as they consider their entire real estate portfolio.
Archive | 2010
Michael Myer; Bruce R. Kinzey; Christine Tam
This a report about a field study of light-emitting diodes street lights by four different manufacturers installed on the FDR Drive in New York City, NY.
Archive | 2009
Bruce R. Kinzey; Michael Myer
This report reviews a demonstration of light-emitting diode (LED) accent lighting compared to halogen (typical) accent lighting in a gallery of the Field Museum in Chicago, IL.
Archive | 2013
Bruce R. Kinzey; Michael P. Royer; M. Hadjian; Rick Kauffman
This report is part of a GATEWAY demonstration that replaced existing HPS streetlights with two different types of LED products and one induction product. Energy savings ranged from 6% to 44%.
Archive | 2009
Bruce R. Kinzey; Michael Myer
This report describes the process and results of a demonstration of solid-state lighting (SSL) technology conducted in 2009 at the recently reconstructed I-35W bridge in Minneapolis, MN. The project was supported under the U.S. Department of Energy (DOE) Solid-State Lighting GATEWAY Technology Demonstration Program. Other participants in the demonstration project included the Minnesota Department of Transportation (Mn/DOT), Federal Highways Administration (FHWA), and BetaLED™ (a division of Ruud Lighting). Pacific Northwest National Laboratory (PNNL) conducted the measurements and analysis of the results. DOE has implemented a three-year evaluation of the LED luminaires in this installation in order to develop new longitudinal field data on LED performance in a challenging, real-world environment. This document provides information through the initial phase of the I-35W bridge project, up to and including the opening of the bridge to the public and the initial feedback received on the LED lighting installation from bridge users. Initial findings of the evaluation are favorable, with minimum energy savings level of 13% for the LED installation relative to the simulated base case using 250W high-pressure sodium (HPS) fixtures. The LEDs had an average illuminance level of 0.91 foot candles compared to 1.29 fc for the HPS lamps. The LED luminaires cost